CW-U SERIES UNITIZED
CURTAINWALL OUTLINE SPECIFICATIONS
The materials used in the
fabrication and installation of this product shall generally
be in accordance with the project specification. The following
minimum standards apply to this particular framing system.
MATERIALS
- Extrusions shall be
6063-T5, 6063-T6, 6063-T54 or 6061-T6, as determined by
the structural engineer certifying the design.
- Formed aluminum shapes
shall be from sheet, alloy and temper suitable for inclusions
within the project.
- All fabrication fasteners
such as screws or nuts and bolts shall be non-corrosive
- stainless steel or, if applicable, fully plated.
- Weathering gaskets
shall be suitable for the application. Gaskets shall be
extruded EPDM or silicone.
- Interior and exterior
gaskets shall have double lip weather seals. Interior
gasket to have joinery sealant applied if vulcanized corners
are not used. Thermal-Break material to have horizontal
and vertical members sealed at intersecting joints.
FINISHES
- Clear Anodized
To be in accordance with the Aluminum Association specification
AA-M12C22A31 class II (.0004") or AA-M12C22A41 class
I (.0007")
- Color Anodized
To be in accordance with the Aluminum Association specification
AA-M12C22A42/44 class I (.0007") unless noted otherwise.
These colors can be light bronze, medium bronze, dark
bronze or black.
- Paint-Thermosetting
type conforming to:
Acrylic or similar finish in accordance with AAMA 603.8
Fluoropolymer finish in accordance with AAMA 605.2. Color
of either finish to be as per project specification.
PERFORMANCE
- Structural design and
performance shall be based on CSA Standard CAN3-S157 "Strength
Design in Aluminum" and as determined by the certifying
Professional Engineer regarding the strength, design and
performance of the framing system. A maximum deflection
of L/175 shall be the minimum standard for the work.
- Air infiltration shall
not exceed 0.06 CFM/ft2 when tested in accordance with
ASTM E283 at a pressure differential of 6.24 P.S.F. There
shall be no water infiltration when tested in accordance
with ASTM331 with a pressure differential of 15.0 P.S.F.
FABRICATION
- All extrusions shall
be accurately cut and fit together with either screw spline
joinery or, if necessary, shear blocks.
- After cutting and before
joinery, all joints shall be wiped clean with recommended
cleaning solvents.
- Joints shall be tightly
fitted and sealed with silicone, or other suitable material
to ensure an airtight and watertight fit.
- All necessary corner
blocks and sealing of same to be factory installed to
bring about individual compartmenting, so that a rain
screen principle of construction is achieved.
- Glass to be installed
in the factory in accordance with outline glazing principles
of F.G.M.A. Install shipping blocks to suit.
- Back pans to be a minimum
of 20 GA galvanized steel with silicone air seals.
- Insulation thickness
and type to be as per the project requirements.
- Insulation impaling
pins to be a minimum of 1 per square foot of insulation
material.
INSTALLATION
- All framing installation
and sealing to be done in accordance with shop drawings
bearing the seal of a registered professional engineer.
Unless noted otherwise, this engineer must also sign off
letters of compliance.
PROTECTION AND CLEANING
- During installation,
all adjacent work shall be protected from damage. After
installation, work shall be left in "wiped clean
condition". Additional protection against damage
from any cause and final cleaning to be done by others.
|